Medium Voltage Filtering Reactor

LTEC produces low voltage and medium voltage reactor in single phase and three phase construction.

Medium Voltage Detuned Reactor

Medium Voltage Filtering Reactor

Technical data

  • Reference standardEN 60076-6

  • Rated voltage≤35KV

  • Rated frequency50Hz

  • Dielectric test50Hz 35KV,60s

  • Cooling methodnatural air

  • Ambient temperature-25 to +50℃

  • Elevation above sea level≤2000m a.s.l.

  • Protection classIP00 indoor mounting

  • Inductance tolerance-2/+3%

  • Blocking factor p%5%-14%

  • Linearity1.55-2.2In

  • Insulation classH

  • Maximum humidity90%

  • Design methodSingle phase or three phase, dry type Iron core, multiple air gap

  • Winding materialCopper/Aluminum

  • TerminalsCopper bar/ CUPONAL bar

Ordering CodeUN((KV)QLC(Kvar)Q(Kvar)UC(KV)LN(mH)IN(A)lrms(A)pfr(Hz)
108% U1,0.5% U3, 6% U5, 5% U7, ILIN =SUM(1.2*IAMP), fN =50Hz, Copper or Aluminum wire winding
LTHR3060132C61321506.63*55.47612.714.36%204
LTHR3060264C2643003*27.72025.428.7
LTHR3060527C5276003*13.88650.757.3
LTHR3060791C7919003*9.25276.186.0
LTHR3061055C105512003*6.937101.5114.7
 
LTHR3070112C61121507.23*77.05010.812.27%189
LTHR3070224C2243003*38.52521.624.4
LTHR3070448C4486003*19.26243.148.7
LTHR3070672C6729003*12.84264.773.1
LTHR307089 6C89612003*9.63186.297.4
 
LTHR3060132A10132150113*154.0997.68.66%204
LTHR3060264A2643003*77.05015.217.2
LTHR3060527A5276003*38.60330.434.4
LTHR3060791A7919003*25.68345.751.6
LTHR3061055A105512003*19.26260.968.8
LTHR3061319A131915003*15.41076.286.1
 
LTHR3070112A10112150123*214.3566.57.37%189
                               
LTHR3070224A2243003*107.17812.914.6
LTHR3070448A4486003*53.46025.929.3
LTHR3070672A6729003*35.69938.843.8
LTHR3070896A89612003*26.76251.758.4
LTHR3071120A112015003*21.39464.773.1
* Other specification are available upon request.                    